Magdaleno-Adame Salvador, Olivares-Galvan Juan Carlos, Escarela-Perez R., Fofana Issouf, Loiselle Luc et Georgilakis P. S.. (2012). Study of parameters influencing the performance of connectors used for load and temperature tests on transformers. Dans : Conference Record of the 2012 IEEE International Symposium on Electrical Insulation (ISEI 2012) , 10-13 june 2012, San Juan, Puerto Rico.
PDF
Administrateurs seulement 3MB |
Résumé
This paper emphasizes the factors to be considered when designing power connectors used in the load and temperature tests of power transformers. External conductors used to perform load and temperature tests in transformers are referred as power connectors in this contribution. Electrical and thermal investigations of a single-phase shell-type, 300 MVA, 400 kV-21.5 kV power transformer connector were performed. To analyze the behavior of the connector, a harmonic analysis to calculate losses by Joule effect generated in the electrical connector was first performed, followed by a thermal, finite element based analysis to determine temperature distribution. As heat sources, harmonic losses analyses were performed. Temperature distribution obtained by the finite element simulation was compared with measurements recorded by an infrared camera during the tests.
Type de document: | Matériel de conférence (Non spécifié) |
---|---|
Date: | 2012 |
Sujets: | Sciences naturelles et génie > Génie > Génie des matériaux et génie métallurgique |
Département, module, service et unité de recherche: | Départements et modules > Département des sciences appliquées > Module d'ingénierie |
Mots-clés: | contact area, electrical conector, finite element method, load test, temperature test, zone de contact, connecteur électrique, méthode des éléments finis, test de charge, test de température |
Déposé le: | 28 janv. 2016 01:22 |
---|---|
Dernière modification: | 18 juill. 2023 18:35 |