Arroyo Fernandez Oscar Henry, Fofana Issouf, Jalbert Jocelyn, Gagnon Sylvie, Rodriguez-Celis Esperanza, Duchesne Steve et Ryadi Mohamed. (2018). Aging characterization of electrical insulation papers impregnated with synthetic ester and mineral oil : correlations between mechanical properties, depolymerization and some chemical markers. IEEE Transactions on Dielectrics and Electrical Insulation, 25, (1), p. 217-227.
Le texte intégral n'est pas disponible pour ce document.
URL officielle: http://dx.doi.org/doi:10.1109/TDEI.2018.006317
Résumé
This article presents a comparative study of two types of transformer solid insulation: standard Kraft and thermally upgraded Kraft papers. The paper samples were impregnated with two different fluids, namely a synthetic dielectric ester fluid, Midel 7131, and a synthesized mineral oil, Luminol Tri. The impregnated papers were submitted to, accelerated aging at 150°C, temperature higher than the temperatures found inside transformers, for extended periods. The results show that for the first hours of aging, the cellulose depolymerization was similar for all the four studied cases. At a specific point, the paper samples aged in the ester fluid exhibited a lower depolymerization exceeding the 8000 hours of aging without reaching the levelling-off degree of polymerization (LODP). A similar trend was observed through the decrease of mechanical properties of papers in the ester-based oil. However, the difference in performance of both fluids was amplified due to the temperature used; at lower temperatures the difference should be smaller. Additionally, a relationship between the degree of polymerization and the mechanical properties accessed by the tensile testing was obtained regardless of the type of paper or oil. The total acidity in the ester fluid was higher than in mineral oil. Methanol, a chemical marker that is closely linked to the rupture of 1,4-β-glycosidic bonds of cellulose, showed a partial sensitivity to the cellulose aging in the ester fluid. Furan (C 4 H 4 O) content was monitored during the aging and its concentration was found to be sensitive to the depolymerization along with the decrease in the mechanical properties of cellulose papers regardless of the type of paper. More importantly, its concentration was found to be dependent on the type of oil. More investigations are needed to further confirm the importance of furan as an indirect indicator of the mechanical performance along with its correlation with the depolymerization of paper aged in ester fluids.
Type de document: | Article publié dans une revue avec comité d'évaluation |
---|---|
Volume: | 25 |
Numéro: | 1 |
Pages: | p. 217-227 |
Version évaluée par les pairs: | Oui |
Date: | Février 2018 |
Sujets: | Sciences naturelles et génie > Génie Sciences naturelles et génie > Génie > Génie électrique et génie électronique Sciences naturelles et génie > Sciences appliquées |
Département, module, service et unité de recherche: | Départements et modules > Département des sciences appliquées > Module d'ingénierie Unités de recherche > Centre international de recherche sur le givrage atmosphérique et l’ingénierie des réseaux électriques (CENGIVRE) > Vieillissement de l’appareillage installé sur les lignes à haute tension (ViAHT) Unités de recherche > Centre international de recherche sur le givrage atmosphérique et l’ingénierie des réseaux électriques (CENGIVRE) |
Mots-clés: | aging, oils, fluids, minerals, power transformer insulation, oil insulation, vieillissement, huiles, fluides, minéraux, isolation de transformateur de puissance, isolation d'huile, Synthetic ester, Midel 7131, high molecular weight acids, low molecular weight acids, mechanical properties, power transformers, degree of polymerization, methanol, ethanol, furan, insulating paper |
Déposé le: | 19 févr. 2021 16:27 |
---|---|
Dernière modification: | 17 août 2021 18:48 |